Thread Series Designator | iso m |
External Actuator Linkage Arrangement | one and two linked |
Thread Pitch In Millimeters | 0.50 |
Center To Center Distance Between Terminals Parallel To Length | 1.940 inches nominal |
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 5000.0 ac all locations |
Reset Method | manual |
Manual Actuator Type And Quantity | 2 toggle |
Circuit Protection Type | overcurrent all locations |
Pole Quantity | 2 |
Mounting Facility Type And Quantity | 4 threaded hole |
Actuator Function | trip-reset |
Operating Voltage Type And Rating Per Pole In Volts | 250.0 ac all locations |
Body Length | 2.480 inches minimum and 2.500 inches maximum |
Fragility Factor | moderately rugged |
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width | 0.750 inches nominal |
Trip Release Method | magnetic all locations |
Actuator Position Designation | at each pole |
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 115.0 all locations |
Case Material | plastic |
Main Contact Tripping Mechanism Type | trip free |
Inclosure Protection Type For Which Designed | moisture resistant and salt spray proof and shock resistant and vibration resistant |
Boss Height | 0.150 inches nominal |
Trip Release Characteristic | time delay all locations |
Frequency In Hertz | 50.0 all locations or 60.0 all locations |
Terminal Type And Quantity | 4 threaded stud |
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 2.050 inches minimum and 2.070 inches maximum |
Nominal Thread Size | 3.0 millimeters |
Mounting Surface To Terminal End Distance | 2.475 inches nominal |
Body Width | 1.500 inches maximum |
Special Handling Feature | magnetic |
Center To Center Distance Between Terminals Parallel To Width | 0.750 inches nominal |
Body Style | multipole-multiple actuator type |
Trip Delay Time In Seconds Per Rated Continuous Current | 0.180 minimum at 200 pct all locations and 1.800 maximum at 200 pct all locations |
Arc Quenching Method | magnetic blowout |
Maximum Continuous Load Current Rating Per Pole | 15.0 amperes ac all locations |
Storage Type | general purpose warehouse |
Internal Trip Release Configuration | series trip all locations |