Overall Height | 1.625 inches nominal |
Trip Release Characteristic | time delay single location |
Frequency In Hertz | 60.0 single location or 1000.0 single location |
Overall Length | 3.625 inches nominal |
Terminal Type And Quantity | 3 screw |
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 4000.0 ac single location and 4000.0 dc single location |
Reset Method | automatic |
Circuit Protection Type | overcurrent single location |
Pole Quantity | 1 |
Trip Release Ambient Temp Rating | 77.0 deg fahrenheit nominal single location |
Mounting Facility Type And Quantity | 2 unthreaded hole |
Unthreaded Mounting Hole Diameter | 0.203 inches nominal |
Operating Voltage Type And Rating Per Pole In Volts | 120.0 ac single location and 28.0 dc single location |
Body Style | rectangular dimensional envelope |
Overall Width | 2.578 inches nominal |
Trip Delay Time In Seconds Per Rated Continuous Current | 10.000 minimum at 200 pct single location and 70.000 maximum at 200 pct single location |
Trip Release Method | thermal single location |
Maximum Continuous Load Current Rating Per Pole | 25.0 amperes ac single location and 25.0 amperes dc single location |
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 138.0 single location |
Case Material | plastic |
Internal Trip Release Configuration | series trip single location |
Inclosure Protection Type For Which Designed | vibration resistant and sand resistant and shock resistant and explosion proof and corrosion resistant |