Thread Series Designator | unc |
Thread Quantity Per Inch | 32 |
Switch Location And Position Designation | internal at pole one |
Switch Current Rating And Type In Amps | 2.5 ac and 1.0 dc |
Maximum Interrupting Capacity Current Type And Rating Per Pole In Amps | 5000.0 ac single location |
Center To Center Distance Between Terminals Parallel To Length | 4.349 inches minimum and 4.369 inches maximum |
Reset Method | manual |
Circuit Protection Type | overcurrent single location |
Pole Quantity | 1 |
Manual Actuator Type And Quantity | 1 toggle |
Mounting Facility Type And Quantity | 4 threaded hole |
Actuator Function | trip-reset |
Operating Voltage Type And Rating Per Pole In Volts | 250.0 ac single location |
Body Length | 5.240 inches minimum and 5.260 inches maximum |
Fragility Factor | moderately rugged |
Distance Between Centerlines Of Mounting Facilities Parallel To Body Width | 0.490 inches minimum and 0.510 inches maximum |
Actuator Position Designation | at pole one |
Trip Release Method | magnetic-hydraulic single location |
Ultimate Trip Rating Of Continuous Current Rating Per Pole In Percent | 125.0 single location |
Main Contact Tripping Mechanism Type | trip free |
Case Material | plastic |
Inclosure Protection Type For Which Designed | dustproof and fungus proof |
Boss Height | 0.209 inches minimum and 0.229 inches maximum |
Switch Terminal Type | tab, solder lug |
Trip Release Characteristic | time delay single location |
Frequency In Hertz | 60.0 single location |
Switch Voltage Rating And Type In Volts | 240.0 ac and 50.0 dc |
Distance Between Centerlines Of Mounting Facilities Parallel To Body Length | 3.052 inches minimum and 3.072 inches maximum |
Nominal Thread Size | 0.164 inches |
Terminal Type And Quantity | 2 threaded stud |
Body Width | 1.490 inches minimum and 1.510 inches maximum |
Special Handling Feature | magnetic |
Auxiliary Switch Function And Quantity | 1 alarm |
Switch Contact Arrangement | single pole, double throw |
Body Style | single pole type |
Trip Delay Time In Seconds Per Rated Continuous Current | 0.350 minimum at 200 pct single location and 1.000 maximum at 200 pct single location |
Arc Quenching Method | magnetic blowout |
Body Height | 2.772 inches minimum and 2.792 inches maximum |
Maximum Continuous Load Current Rating Per Pole | 60.0 amperes ac single location |
Storage Type | general purpose warehouse |
Internal Trip Release Configuration | series trip single location |